1-Wire air quality sensor Pro I UP for Berker, Jung, Merten

€126.63 *

Prices incl. VAT plus shipping costs

Ready to ship today,
Delivery time appr. 1-3 workdays

Central plate / covers / panels:

  • 11161.1
Elegant air quality sensor for 1-Wire bus system for private and commercial use -... more
Product information "1-Wire air quality sensor Pro I UP for Berker, Jung, Merten"

Elegant air quality sensor for 1-Wire bus system for private and commercial use

- Sensitive air quality sensor
- Processing of the sensor values, therefore no complex formulas necessary -
wall sensor (flush-mounted)

1-Wire flush-mounted air quality

With the 1-Wire air quality sensor (called VOC or air quality) a simple monitoring of the indoor climate is possible. The 1-Wire air quality sensor works with a VOC mixed gas sensor, which detects different substances in the ambient air, similar to the human nose.
The air quality sensor is very well suited for working rooms in schools, commercial and private areas.
With the help of the air quality sensor, a statement on the current air quality and advice on ventilation can be given. An air system can also be controlled according to demand.

The 1-Wire air quality sensor is supplied incl. central plate and adapter frame in white high gloss or matt for all 50/55mm switch ranges. The air quality sensor is for all switch ranges with 50mm and 55mm dimensions of the central disc, e.g. for Berker, Jung, Merten and many others.
If you need a different colour of the central disc, please contact us.


The air quality sensor outputs measured values for air quality and its operating voltage.

1-Wire interface

DS2438 command set, sensor for air quality and operating voltage

Air quality

Measuring range 400 - 2000ppm (CO2 equivalent)

Resolution

1 ppm (CO2 equivalent)

Operating temperature

5 - 40°C

1-Wire connection

3 - conductor connection (data, ground and 5V, parasitic operation not supported)

Operating voltage

5 VDC +/-10%

Power consumption

approx. 45 mA

Connection:

Push In Terminal, screwless terminal

Dimensions (outside)

71 x 71 x 37 mm (LxWxH)

Scope of delivery

Sensor module, central plate (orifice), adapter ring + operating instructions

Note: Unfortunately the Loxone 1-Wire Extension does not support the functionality of the module, we recommend the use of the 1-Wire Controller or 1-Wire Gateway.

Assembly: Unterputz
Measured values: Temperatur
Function: Sensorik
Design: Berker, Jung, Merten
Downloads & Links
Read, write and discuss reviews... more
Customer evaluation for "1-Wire air quality sensor Pro I UP for Berker, Jung, Merten"
Write an evaluation
Evaluations will be activated after verification.
Please enter these characters in the following text field.

The fields marked with * are required.

Viewed